fire dampers
Sleeves and Attachment
Construction and specifications :
Frame :
20 Ga (1mm) galvanized steel frame.
Blades :
24 Ga (0.7mm) interlocking type galvanized steel.
Fusible link :
U.L Listed standard F fusing temperature. (other temperatures available on request)
Mounting :
Vertical & horizontal mounting positions.
Fire rating :
1 1/2 hour rated for use in 1 hour or 2 hours partitions.
Springs :
constant force closure springs.
Sealing :
side seals. . Finish. All steel parts with gal vanized mill finish.
Single section :
minimum size 6” x 6” W x H. Inch
maximum size 40” x 40” W x H. Inch.
Free area :
55-78% of Nominal
Recommended :
for low – medium air velocities.
Construction and specifications
Frame :
Made from high quality galvanized steel gauge 16.
Stainless steel frame is
Blade :
Made from high quality galvanized steel
gauge 22.
Stainless steel blades are available as
option
Blade ramp :
Frome galvanized steel with aspring holder Closure spring
Made from stainless steel spring
Fusible links :
UL listed Fusible links which has fire rating
of 165oF / 212 oF
Installation
Sleeve
Performance data
Data Sheet
Construction and specifications
Operating temperatures : 135F, 165F,212F,286F,350F,375F.
Underwriters laboratory listed : yes.
Loading :
Minimum: 1 Ibs
Maximum : 10 Ibs
Size :
Length :1.500 inches
Width : .562 inches
Distance between centers : .930 inches
Material :
Stamping :steel
Solder : bismuth alloy
Unit weight : .16 Ibs
Available with long or short hooks : yes
For specific fusible link ratings.
Many other temperature available ( non – UL listed )
Numbers derived from underwriters laboratories standard UL 33
Fusible Links
See General Information for Fusible Links
ELSIE MFG CO INC
600 W MAPLE ST
PO BOX 97
WATERLOO, IN 46793 USA
Issue A, in the 135, 165, 212, 225, 350, 360, 370, 386°F temperature ratings. For loads from 1 to 30 lbs incl Bearing length 2 in.
Issue AM, in the 165°F temperature rating. For loads from 1 to 30 bs. incl. Bearing length 2 in. Issue B, in the 135, 165, 212, 286, 350, 375°F temperature ratings. For loads from 1 to 10 lbs incl Bearing length 1-3/16 in.
Issue C, in the 165, 212, 370°F temperature ratings. For loads from 2 to 50 lbs incl. Bearing length 3-3/8 in.
Issue D, in the 165, 212, 285, 286°F temperature ratings. For loads from 1 to 40 lbs incl. Bearing length 2 in.
Issue E, in the 165, 212, 286, 350, 360°F temperature ratings. For loads from 2 to 50 lbs incl Bearing length 1-1/4 in.
Issue GFC housing frame, in the 165, 212°F temperature ratings. For loads from 4 to 40 bs inel. Issue Y, in the 165, 212°F temperature ratings. For loads from 1.25 to 40 lbs incl.
Last Updated on 2008-11-20
©2013 UL LLC
When the UL Leaf Mark is on the product, or when the word “Environment” is included in the UL Mark, please search the UL Environment database for additional information regarding this product’s certification.
The appearance of a company’s name or product in this database does not in itself assure that products so identified have been manufactured under UL’s Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL’s Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assembles, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement “Reprinted from the Online Certifications Directory with permission from UL” must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
“©2013 UL LLC”.
How To Order